Mitsubishi Electronics AJ65bt-r2 Manual Do Utilizador

Página de 264
4 - 11
MELSEC-A
4   PROCEDURES AND SETTINGS BEFORE OPERATION
4.6 Checking the module's state (Hardware test)
Confirm that the R2 operates normally as a single module. Always carry out this test
before structuring the system.
Execute the test with the following procedure.
Set the data link related hardware.
·
 
Set the data link transmission speed setting switch.
Start
Disconnect the CC-Link dedicated cable for 
the data link from R2.
Mount an RS-232-C single module loopback connector. 
Set the mode setting switch to "D". 
(hardware test mode)
Turn ON the R2 power.
Confirm the RS-232-C ERR. LED 
*
2
*
1
 *1
The specifications of the RS-232-C single module loopback connector are shown
below.
Create the RS-232-C single module loopback connector shown below.
R2 side (DTE)
Signal abbrev.
Pin No.
Single module loopback
connector
CD
1
RD (RXD)
2
SD (TXD)
3
DTR (ER)
4
SG
5
DSR (DR)
6
RS (RTS)
7
CS (CTS)
8
9
IMPORTANT
During the hardware test mode, the check data is transmitted to the data link when
checking the data link loopback, so always disconnect the data link wiring.