Справочник Пользователя для Mitsubishi Electronics FX5

Скачать
Страница из 306
19  BUILT-IN I/O FUNCTION
19.1  High-speed Counter Function
129
19
High-speed counter (rotational speed measurement mode)
The rotational speed measurement mode for high-speed counters is explained below.
When in rotational speed measurement mode, pulse is counted from count input of the high-speed counter, and the rotational 
speed for a specified amount of time is automatically calculated.
Set operation mode to rotational speed measurement mode by high-speed counter parameter setting.
Sets detailed settings for channel used.
Navigation window  [Parameter]  [FX5UCPU]  [Module Parameter]  [High Speed I/O]  “Input Function"  “High 
Speed Counter"  "Detail Setting"  “Basic Setting"
Window
Displayed items
Item
Description
Setting range
Default
Use/Not Use
Set whether use counter or not.
• Disable
• Enable
Disable
Operation Mode
Set operation mode.
• Normal Mode
• Pulse Density Assumption Mode
• Rotation Speed Measurement 
Mode
Pulse Input Mode
Set pulse input mode.
• 1-Phase 1 Input (S/W Up/Down 
Switch)
• 1-Phase 1 Input (H/W Up/Down 
Switch)
• 1 Phase 2 Input
• 2 Phase 1 Multiple
• 2 Phase 2 Multiple
• 2 Phase 4 Multiple
• Internal Clock (1MHz)