1  PROGRAM EXECUTION
1.1  Scan Configuration
17
1
I/O refresh
Execute I/O refresh before starting program operations.
 • Input ON/OFF data input from input module/intelligent function module to CPU module
 • Output ON/OFF data input from CPU module to output module/intelligent function module
When executing constant scan, I/O refresh is executed after the constant scan waiting time ends.
Program operations
Step 0 of each program up to the END/FEND instruction is executed according to program settings. This program is called the 
"main routine." Main routine programs can be divided into subroutines. (Page 29 Subroutine program)
END processing
END processing involves the following processes:
 • Refreshing of network modules
 • Refreshing of intelligent function modules
 • Instruction termination processing
 • Device/label access service processing
 • Resetting of the watchdog timer
 • Self-diagnostic processing
 • Setting of values to special relays/special registers (set timing: when END processing is executed)