20  BUILT-IN ANALOG FUNCTION
20.2  Analog Input/Output Specifications
List of analog input functions
List of analog output functions
List of Functions
Description
Function to enable/disable A/D conversion
Function to enable or disable A/D conversion per channel.
The conversion process time can be reduced by disabling conversion for unused channels.
A/D conversion 
method
Sampling processing
Method of converting each analog input at END processing to generate the equivalent digital output.
Count average
Method of averaging the count of A/D conversion values and outputting these average values as the digital 
signal.
Time average
Method of averaging the time of A/D conversion values and outputting these average values as the digital 
signal.
Moving average
Method of averaging the analog input for a specified count measured at every END process, and outputting 
these average values as the digital signal.
Function to detect over-scale
Function to detect analog input values that are over a specified range.
Scaling function
Function that converts user-defined maximum and minimum digital values in accordance with a configured 
scale.
Shift function
Function that adds a specified amount to the A/D conversion value.
Fine adjustments during system startup can be easily performed.
Digital clipping function
Function that specifies the maximum A/D conversion value as 4000 and the minimum value as 0 when 
voltage is input that exceeds the input range.
Function to hold minimum and maximum values
Function that holds the minimum and maximum digital operation values.
Warning output function
Function to output warning when digital operation values exceed the specified range.
List of Functions
Description
Function to enable/disable D/A conversion
Function to enable or disable D/A conversion.
When analog output is not used, the conversion process time can be reduced by disabling conversion.
Function to enable/disable D/A output
Specifies whether to output the D/A conversion value or output an offset value (HOLD setting value).
Scaling function
Function that converts user-defined maximum and minimum digital values in accordance with a configured 
scale.
Shift function
Function that adds a specified amount to the digital value.
Fine adjustments during system startup can be easily performed.
Function to HOLD/CLEAR the analog output
Sets the digital value before D/A conversion to the previous value or clears the value (0) depending on the 
operation status of the CPU module (RUN, STOP, and STOP error).
Analog test when the CPU module has stopped
Outputs a user-defined analog value by setting the output enable/disable flag to enabled when the CPU 
module is stopped, and changing the digital value.
Warning output function
Function to output warning when digital values exceed the specified range.