11  REMOTE OPERATION
11.3  Remote RESET
89
11
Precautions
When keeping in forced ON or OFF status in advance
When keeping in forced ON or OFF status in advance, interlock using the PAUSE contact (SM204).
11.3
Remote RESET
This is an operation to reset the CPU module by an external operation when the CPU module is in the STOP status. In 
addition, even if the RUN/STOP/RESET switch of the CPU module is set to RUN position, reset is possible when the CPU 
module has stopped due to occurrence of an error that can be detected by self-diagnosis function.
Application of remote RESET
When a CPU module is in an inaccessible place and an error has occurred, CPU module can be reset by a remote operation.
Enabling remote RESET
To remotely RESET, remote RESET must be enabled.
Navigation window  [Parameter]  [FX5UCPU]  [CPU Parameter]  "Operation Related Setting"  "Remote Reset 
Setting"
Window
Displayed items
Item
Description
Setting range
Default
Remote Reset
Set whether or not to enable remote RESET.
• Disable
• Enable
Disable
SM204
M0
Y72
Turns ON in PAUSE status.
SM204
X0
Y71
Turns OFF in PAUSE status.
M20
Y70
The ON/OFF status of Y70 is determined by 
the ON/OFF status of M20 in PAUSE status.