Справочник Пользователя для Mitsubishi Electronics QJ71LP21GE

Скачать
Страница из 400
 
 
 
4 - 32                                                                                                                                                       4 - 32 
MELSEC-Q
4   SETTING AND PROCEDURE BEFORE OPERATION 
 
4.10 Network Diagnostics from GX Developer (Online Tests) 
With the network diagnostic function of GX Developer, the line status can easily be 
checked and diagnosed. 
Conduct network diagnostics by connecting GX Developer with a remote master 
station. 
For a remote sub-master station and remote I/O station, the line status can be 
confirmed through the network diagnostics of the remote master station. 
To conduct the network diagnostics, the network parameters (station number setting 
switches, mode setting switch, number of modules, network settings, and common 
parameters) must be set. 
However, even if not all the parameters were set, the loop test can be performed while 
the T.PASS LED is on. 
The network diagnostics function allows the diagnostics of the network module while 
maintaining it in the online status when a problem occurs during system operation. 
The following table lists the tests that can be conducted for each network system: 
 
Test item 
Optical loop 
system 
Coaxial loop 
system 
Data link status of cyclic 
and transient 
transmissions 
Reference 
section 
Network test 
 
 Continue 
Section 
7.9 
Loop test 
 
 
Pause Section 
4.10.1 
Setup confirmation test 
 
 
Pause Section 
4.10.2 
Station order check test 
 
 
Pause Section 
4.10.3 
Communication test 
 
 Continue 
Section 
4.10.4 
: Execution allowed   : Execution not allowed 
 
For details on the operations of each function, refer to the GX Developer Operating 
Manual. 
 
The following screen is displayed when the network diagnostics is selected with GX 
Developer. Select the button for the network diagnostic item that will be conducted. 
 
Select a test.