A - 18                                                                                                                                                  A - 18 
 
DEFINITIONS OF TERMINOLOGY 
Term Description 
Cyclic transmission 
Function by which data communications are performed periodically between a remote master 
station and remote I/O stations using link devices (LB/LW/LX/LY) of network modules. 
Transient transmission 
This function allows communication with another station's programmable controller when a 
request is made with a link dedicated instruction or from GX Developer. 
Communications can be made with programmable controllers on the same or other networks.
Link dedicated instruction 
Dedicated instruction used for transient transmission. 
RAS 
The abbreviation for Reliability, Availability, and Serviceability. 
This term is used to express the overall usability of automation systems. 
Remote master station 
Master station on a remote I/O network 
Remote I/O station 
Station that performs cyclic transmission according to the range assignment of the remote 
master station. 
MELSECNET/10 mode 
A mode to operate the MELSECNET/H remote I/O module on the MELSECNET/10 remote 
I/O network 
MELSECNET/H 
(MELSECNET/10 mode) 
remote I/O station 
A remote I/O station where the MELSECNET/H remote I/O module is being operated in 
MELSECNET/10 mode 
Reserved station 
Station that is not actually connected to the network. 
It must be included in the total number of stations in the network, since it is to be connected 
in the future. 
Relay station 
Station that relays transient transmission data to another network. 
Link device data of a network module are transferred to another network module via this 
station. 
Multiple network modules are connected to one programmable controller. 
Reconnection 
Processing of restarting data link when a faulty station becomes normal. 
Disconnection 
Processing of stopping data link when a data link error occurs. 
Device 
Devices (X, Y, M, D, etc.) that are contained in a CPU module. 
Link Device 
Devices (LB/LW/LX/LY) that are contained in a network module. 
Link scan time 
Time required for data of each station to be sent in order and to make one rotation in the 
network. 
The link scan time changes depending on the data volume or transient transmission request.
Link refresh 
On the remote master station, data are transferred between the master module's link devices 
and the CPU module's devices. Link refresh means this processing. 
Link refresh is performed in "END processing" of the sequence scan of the CPU module. 
I/O refresh 
On a remote I/O station, data are transferred between remote I/O module's link devices and 
the following devices.  I/O refresh means this processing. 
• I/O module's devices 
• Intelligent function module’s devices 
Automatic refresh 
On a remote I/O station, data are transferred between remote I/O module's link devices and 
intelligent function module's devices. Automatic refresh means this processing. 
Buffer memory 
Memory area in an intelligent function module, in which data are temporarily stored. 
The network module does not have any buffer memory area that is offered to the user. 
Baton pass 
A control mechanism in which transmission right (token) is passed around the network for 
data transmission. 
Group No. 
Number that is assigned for transient transmission to any given stations. 
By specifying a group of stations as transient transmission target, data can be sent to the 
stations of the same group No.