7   APPLICATION FUNCTIONS 
 
7.10 Multiplexed remote master function (Process CPU) 
The multiplex remote master function allows the multiplexed remote sub-master station 
to take control of the remote I/O stations when the multiplexed remote master station 
fails. 
 
Multiplexed remote 
master station
Multiplexed remote 
sub-master station
Remote I/O station Remote I/O station
Remote I/O station
 
 
The multiplexed remote master function has the following merits. 
Item Description 
(1) Continuation of controlling remote 
I/O stations when multiplexed 
remote master station becomes 
faulty 
The multiplexed remote sub-master station (DSM
R
) takes control of the remote 
I/O stations (R), when the multiplexed remote master station (DM
R
) becomes 
fails. 
(2) Selection of operating station 
status when multiplexed remote 
master station returns to system 
It is possible to set parameter to select the operating station status when the 
multiplexed remote master station returns to the system. 
Return to system as control station  
The master operating station (control station) is switched from the multiplexed 
remote sub-master station (DSM
R
) to the multiplexed remote master station 
(DM
R
). 
At the time of switching, the remote I/O stations are reset once. 
Return to system as standby station  
The multiplexed remote sub-master station (DSM
R
) operates continuously as 
the master operating station (control station). 
Furthermore, when the multiplexed remote master station has returned to the 
system as the sub-master operating station (standby station), it is switched to 
the master operating station (control station) manually. 
(3) Startup of a multiplexed remote 
sub-master station only 
By setting the same parameters as the multiplexed remote master station 
(DM
R
), the multiplexed remote sub-master station (DSM
R
) can resume control 
of remote I/O stations if it is powered on and off while controlling the remote I/O 
stations (in case that the multiplexed remote master station has been faulty).