7.11 Multiplexed remote master function for the redundant system (Redundant CPU) 
The redundant system uses the multiplexed remote master function to control I/O 
modules and intelligent function modules. 
The multiplexed remote master function for the redundant system continues the control 
of remote I/O stations when the multiplexed remote master station (control system) 
fails by switching the multiplexed remote master station from the control system to the 
standby system and switching the multiplexed remote sub-master station (standby 
system) from the standby system to the control system. 
The multiplexed remote sub-master station (control system) which is controlling a 
remote I/O station continues the control of the remote I/O station even after the 
multiplexed remote master station (standby system) returns to the normal status. 
 
Multiplexed remote master station (DM
R
)
Control system     Standby system
Multiplexed remote sub-master station (DSM
R
)
Standby system     Control system
Remote I/O station (R) Remote I/O station (R) Remote I/O station (R)
Tracking cable
 
 
The multiplexed remote master function for the redundant system includes the 
following features. 
 
Item Description 
Reference 
section
(1)  Backup function of master 
operation on system 
switching between control 
system and standby system 
When a power supply error or CPU error occurs in the control system, the 
Redundant CPU in the standby system continues the operation of the redundant 
system by switching to the control system. With the system switching, the 
multiplexed remote sub-master station switched from the standby system to the 
control system takes over master operation to continue the control of remote I/O 
stations. 
Section 7.11.1
 
(2)  Master operation by the 
station that has started up as 
the control system 
The master module mounted with the Redundant CPU that has started up as the 
control system operates as the master station. The master module mounted with the 
CPU that has started up as the standby system operates as the sub-master station. 
Section 7.11.2
 
(3) System switching request 
function of control system 
The master module mounted in the control system CPU issues the system switching 
request to the control system CPU when a data link error such as link cable 
disconnection or transmission error are detected. 
Section 7.11.3
 
(4)  Access function by specifying 
control system or standby 
system 
Access from GX Developer or others to Redundant CPU can be performed by 
specifying the control system/standby system instead of station No. Therefore, the 
control system can be accessed any time even if system is switched. 
Section 7.11.4
 
 
(1)  Network parameter settings 
It is not required to create each project for control system/standby system. In a 
redundant system, parameters and sequence programs common to both 
systems can be created in one project.