Справочник Пользователя для Mitsubishi Electronics QJ71LP21GE

Скачать
Страница из 400
 
 
 
7 - 35                                                                                                                                                                                                          7 - 35 
MELSEC-Q
7   APPLICATION FUNCTIONS 
 
(d)  The output of the remote I/O station is held while master operation is 
switched from the multiplexed remote master station to the multiplexed 
remote sub-master station. 
 
Multiplexed remote master station
Multiplexed remote sub-master station
Remote I/O station Remote I/O station Remote I/O station
Output is held during system switching.
 
 
(e)  If the multiplexed remote master station returns to the normal status while 
the multiplexed remote sub-master station controls remote I/O stations, the 
multiplexed remote master station will perform sub-master operation as the 
standby system. 
 
Multiplexed remote master station 
(standby system)
Multiplexed remote sub-master station 
(control system)
Remote I/O station
Remote I/O station
Remote I/O station
Master operation
Sub-master operation
 
 
7.11.2 Master operation by the station that has started up as the control system 
The master module mounted in the station that has started up as the control system 
performs master operation. The master module mounted in the standby system station 
performs sub-master operation. 
 
REMARKS 
For the determination of the control system or standby system, refer to the 
QnPRHCPU User's Manual (Redundant System). 
 
Which of the multiplexed remote master station or multiplexed remote sub-master 
station are controlling remote I/O stations can be checked from the MNG LED of each 
station. 
 
RUN
MNG
T.PASS
D.LINK
SD
RD
ERR.
L ERR.
QJ71BR11
On: master operation (station controlling remote I/O stations)
Off: sub-master operation