8   TROUBLESHOOTING 
 
8.2.7 Items checked when multiplexed remote I/O network for redundant system does not 
operate normally 
(1)  Redundant CPU does not perform system switching even when the 
data link cable is disconnected. 
 
Check item 
Checking procedure 
Isn't the power supply module of the standby 
system turned off? 
Confirm the status of the external power supply of the standby system. 
Hasn’t a stop error occurred in the standby system 
CPU? 
Connect GX Developer to the standby system CPU and execute PLC diagnostics to 
check if any error has occurred. 
Hasn’t an error occurred in the master module 
mounted on the main base unit of the standby 
system? 
Confirm the operation status of the master module of the standby system. 
 
(2)  Errors on a remote I/O station cannot be detected by the 
programmable controller CPU of the master operation station. 
 
Check item 
Checking procedure 
Hasn’t an error occurred on a remote I/O station 
with function version C or earlier? 
Check the product information of the remote I/O module of the remote I/O station by the 
system monitor of GX Developer. 
 
(3)  Cyclic data are turned off continuously or instantaneously when 
system switching is performed on Redundant CPU. 
 
Check item 
Checking procedure 
Is the send range of the host a tracking range? 
Confirm if the devices in the send range of the host is set as tracking devices with the 
parameters of GX Developer. 
 
 
8.2.8 Items checked when a minor error (continue error) on a remote I/O station cannot be 
detected 
Check item 
Check procedure 
Has SB000F of the remote master station turned 
ON? 
Turn OFF SB000F of the remote master station.