8   TROUBLESHOOTING 
 
8.3.2 MELSECNET/H error code list 
 
Table 8.1 Error code list 
Error code 
Description 
Corrective action 
4000 to 4FFF 
(Error detected by the programmable 
controller CPU) 
Take measures referring to the QCPU User's Manual (Hardware Design, 
Maintenance and Inspection). 
7000 to 7FFF 
(Error detected by the serial 
communication module, etc.) 
Take measures referring to the troubleshooting section of the Serial 
Communication Module User's Manual. 
B000 to BFFF  (Error detected by the CC-Link module) 
Take measures referring to the troubleshooting section of the CC-Link System 
Master/Local Module User's Manual. 
C000 to CFFF (Error detected by the Ethernet module) 
Take measures referring to the troubleshooting section of the Ethernet Interface 
Module User's Manual. 
D000 to DFFF 
(Error detected by CC-Link IE Field 
Network) 
Take measures referring to the troubleshooting section of the CC-Link IE Field 
Network User’s Manual. 
E000 to EFFF 
(Error detected by CC-Link IE Controller 
Network) 
Take measures referring to the troubleshooting section of the CC-Link IE 
Controller Network Reference Manual. 
F101 
Initial status (Network activated) 
Wait until SB0047 (baton pass status) and SB0049 (data link status) turn off 
(normal). 
F102 
Initial status (Network activated) 
F103 
Initial status (during online test) 
F104 
Initial status   
(Control/sub-control station shift) 
F105 
Initial status (Parameters being processed)
F106 
Shift from failed control station to sub-
control station 
Check the condition of the control station's power supply and of the cables and 
the status of the control station CPU module. 
F107 
Baton pass error (baton lost) 
Check the line status for a faulty cable or a missing terminating resistor, as well 
as the stations that are not powered on. 
In the case of the PLC to PLC network, when transient transmission is 
executed frequently and the link scan time may exceed 200 ms, adjust the 
transient setting values to reduce the link scan time. 
F108 
Baton pass error (duplicate baton) 
Execute a setup confirmation test to check whether the same station number 
has been set for two or more stations or whether two or more control stations 
exist. 
Check for faulty cables, wire breakage, poor connector connections, connection 
errors, uninstalled or loose terminating resistors, etc. 
F109 
Initial status (during online test) 
Wait until SB0047 (baton pass status) and SB0049 (data link status) are 
recovered. 
F10A 
Initial status (online test/offline loop test) 
<During execution of an online test> 
Wait until SB0047 (baton pass status) and SB0049 (data link status) are 
recovered. 
<During execution of an offline test> 
Change the switch setting to online after the test has been completed. 
F10B 
Duplicate station number error 
Review the station number setting. 
The setup confirmation test of network diagnosis is effective. 
F10C 
Duplicate control station error 
Review the station number setting. 
The setup confirmation test of network diagnosis is effective. 
F10D 
Offline status 
Review the mode setting, and change it to online. 
F10E 
Number of receive error retries exceeded  Check for faulty cables, faulty hardware, incorrect cable wiring, and absence of 
terminating resistor (in the case of the bus). In addition, check whether the 
same station number has been set for two or more stations or whether two or 
more control stations or remote master stations exist.   
The setup confirmation test and loop test of network diagnosis are effective. 
F10F 
Number of send error retries exceeded 
F110 
Timeout error