Справочник Пользователя для Mitsubishi Electronics QJ71LP21GE

Скачать
Страница из 400
 
 
 
App - 3                                                                                                                                                     App - 3 
MELSEC-Q
APPENDICES 
 
Appendix 2 Link Special Relay (SB) 
The link special relay (SB) turns on/off by various factors that occur during data linking. 
Thus, by monitoring or using it in the sequence program, the abnormal status of the 
data link can be checked. 
Moreover, the link special relays (SB) that stores the link status are used for the 
detailed information of the network diagnostics of GX Developer. 
For a list of the device numbers for each display item, see Section 8.1 "Network 
Diagnostics (Network Monitor)" and Section 8.3.1 "How to check error codes" 
 
(1)  When multiple network modules are mounted 
Data in the link special relay (SB) of each network module are refreshed to the 
following link special relay (SB) areas of the CPU module when the refresh 
parameters of each network module are set to their default. 
 
Module mounting position
Module 1 
Module 2 
Module 3 
Module 4 
Device number 
SB0000 to 01FF SB0200 to 03FF SB0400 to 05FF SB0600 to 07FF
 
(2)  Range turned ON/OFF by user and range turned ON/OFF by 
system 
The link special relay (SB) has the user setting area range (SB0000 to SB001F) 
and the system setting area range (SB0020 to SB01FF). (The device numbers 
are the example when the network module is mounted in the position of Module 
1.)