MELSEC-Q
2   SYSTEM CONFIGURATION 
 
2.2.2 Setting items 
(1)  Table 2.3 lists the parameter setting items of the multiplexed remote master 
station (DM
R
) and multiplexed remote sub-master station (DSM
R
). 
 
Table 2.3 Setting Items of Multiplexed Remote Master Station and 
Multiplexed Remote Sub-Master Station 
Setting item 
Multiplexed remote 
master station (DM
R
Multiplexed remote 
sub-master station 
(DSM
R
Reference 
Network module switch 
 
 
 
STATION NO. 
1 to 64 
Section 4.2.1 
 MODE 
Section 4.2.1 
Parameter setting on GX Developer  
 
 
  Setting the number of Ethernet/CC IE/MELSECNET cards 
 
   
Network type 
MELSECNET/H  
(Multiplexed remote 
master station) 
MELSECNET/H  
(Multiplexed remote 
sub-master station) 
Section 5.1.1 
  Starting 
I/O 
Section 5.1.2 
  Network 
No. 
Section 5.1.2 
  Total 
stations 
1
 
Section 5.1.2 
  Group 
No. 
Section 5.1.2 
  Mode 
Section 5.1.2 
 Common 
parameters 
1
 
Section 5.1.3 
 Supplementary 
setting 
Section 5.1.4 
  Station specific parameters 
— 
 Refresh 
parameters 
2
3
 
2
3
 
Section 5.1.5 
  Valid module during other 
station access 
 
 
Section 5.1.6 
  Interlink transmission parameter
— 
 Routing 
parameters 
: Always set,  : Default setting,  : Set as needed,  : No need to set 
 
POINT 
 
1: Set Total stations and common parameters of the multiplexed remote sub-
master station when using the multiplexed remote sub-master station to 
resume the network. The settings must be the same as those of the 
multiplexed remote master station. 
For example, if the multiplexed remote master station is powered off and then 
on during network control by the multiplexed remote sub-master station, the 
multiplexed remote sub-master station resumes networking as a master 
operating station. 
 
2 : Default values are not set in LX/LY. Set the refresh parameters. 
3 : Default values are preset for LB/LW. 
The system may operate even if refresh parameters have not been set. 
For the operation and precautions, refer to Section 5.1.5 (3). 
4 : Refer to the Q Corresponding MELSECNET/H Network System Reference 
Manual (PLC to PLC Network) (SH-080049).