5  SEQUENCE INSTRUCTIONS
5.3  Output Instructions
151
5
Low-speed timer, high-speed timer, low-speed retentive timer, 
high-speed retentive timer
OUT T, OUTH T, OUT ST, OUTH ST
*1 The value setting for the timer cannot be designated indirectly.
See Page 106 Indirect Specification for further information on indirect designation.
*2 Timer values can be set only as a decimal constant (K). Hexadecimal constants (H) and real numbers cannot be used for timer settings.
(D):   Timer number (bit)
Setting value  Value set for timer (BIN 16 bits
Setting 
data
Internal device
R, ZR
J\
U\G
Zn
Constant
K
Others
Bit
Word
Bit
Word
(D)
 (Only T, 
ST)
Set value
 (Other 
than T, ST, 
C)
Basic
Process
High
performance
Redundant Universal
LCPU
T0
Set value
Setting in the range 
from 1 to 32767 is valid.
K50
T0
Set value
Data register value in 
the range from 1 to 
32767 is valid.
D10
T0
Set value
Setting in the range 
from 1 to 32767 is valid.
K50
H
T0
Set value
Data register value in 
the range from 1 to 
32767 is valid.
D10
H
ST0
Set value
Setting in the range 
from 1 to 32767 is valid.
K50
ST0
Set value
Data register value in 
the range from 1 to 
32767 is valid.
D10
ST0
Set value
Setting in the range 
from 1 to 32767 is valid.
K50
H
ST0
Set value
Data register value in 
the range from 1 to 
32767 is valid.
D10
H
OUT T
OUTH T
OUT ST
OUTH ST
Command
Command
Command
Command
Command
Command
Command
Command
(High-speed retentive timer)
(Low-speed timer)
(High-speed timer)
(Low-speed retentive timer)
@D0
T0
Indirect designation is 
not permitted.