CHAPTER 3 BEFORE USING I/O MODULE
3
3.
2  
O
u
tput
 Mo
dul
e
3.2
Output Module
(1) Common precautions for all output modules
(a) Maximum switching frequency when the module drives Inductive load.
The output must be on for one second or longer and off for one second or longer.
(b) Load for connection
When connecting a counter or timer that has a DC-DC converter as a load, select an output module whose 
maximum load current is larger than inrush current of the load.
Selecting an output module by average current of the load may cause a failure of the module because inrush 
current flows at a constant frequency at power-on or during operation due to the connected load.
If an output module needs to be selected by average current of the load, take either of the following actions to 
reduce an influence from inrush current.
• Connecting a resistor to the load in series
• Connecting an inductor to the load in series
Output  
module
Resistor
Load
Output  
module
Inductor Load