Справочник Пользователя для Mitsubishi Electronics LH42C4NT1P

Скачать
Страница из 102
39
CHAPTER 4 SPECIFICATIONS
4
4.
3  
O
u
tput
 Mo
dul
e
 Spe
cif
icat
ions
4.3.1
LY10R2 contact output module
Item
Specifications
Appearance
Number of output points
16 points
Rated switching voltage, current
24VDC 2A (resistance load)/point, 8A/common
240VAC 2A (COS
 = 1)/point, 8A/common
Minimum switching load
5VDC 1mA
Maximum switching load
264VAC 125VDC
Response time
OFF to ON
10ms or less
ON to OFF
12ms or less
Life
Mechanical
20 million times or more
Electrical
Maximum switching frequency
3600 times/hour
Surge suppressor
None
Fuse
None
Dielectric withstand voltage
2300VAC, 1 minute (altitude 2000m)
Insulation resistance
10M
 or more by insulation resistance tester
Noise immunity
By noise simulator of 1500Vp-p noise voltage, 1µs noise width and 25 to 60Hz 
noise frequency
Protection degree
IP1X
Common terminal arrangement
16 points/common (common terminal: TB17)
Number of occupied I/O points
16 points (I/O assignment: output 16 points)
External interface
18-point screw terminal block (M3 × 6 screws) (
5VDC internal current 
consumption
460mA (TYP. all points ON)
Weight
0.21kg
External connections
Terminal connections
TB1
Load
Load
LED
TB17 
TB16
LED
100/200VAC
or
24VDC
Internal  
circuit
Relay
Relay
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
Y01
Y03
Y05
Y07
Y09
Y0B
Y0D
Y0F
Y00
Y02
Y04
Y06
Y08
Y0A
Y0C
Y0E
COM
Empty
The following diagram shows the external load power supply.
100/200VAC  
or   
24VDC
External load  
power supply
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Terminal
number
Signal
name
Signal
name
Viewed from the front of the module.