CHAPTER 9
PROGRAMMING
This chapter describes the programming of the D/A converter module.
9.1
Precautions for Programming
This section describes precautions to create CC-Link IE Field Network programs.
(1) Cyclic transmission program
For a cyclic transmission program, interlock with the following link special relay (SB) and link special register 
(SW).
 • Own station data link status (master station) (SB0049)
 • Data link status (each station) (SW00B0 to SW00B7)
For the link special relay (SB) and link special register (SW), refer to the following.
 User's manual for the master/local module used
Ex.
Interlock example
(2) Transient transmission program
For a transient transmission program, interlock with the following link special relay (SB) and link special register 
(SW).
 • Own station baton pass status (master station) (SB0047)
 • Baton pass status (each station) (SW00A0 to SW00A7)
For the link special relay (SB) and link special register (SW), refer to the following.
 User's manual for the master/local module used
Ex.
Interlock example
Communication program with station No.1
Communication program with station No.2
Dedicated instruction to station No.1
Start contact