Appendix 1
Details of Remote I/O Signals
This section describes the details of remote I/O signals assigned to the master/local module.
The assignment of each device number is for the case when the remote I/O signals of the main module are assigned 
as follows.
 • Remote input signal: RX0 to RX1F
 • Remote output signal: RY0 to RY1F
Appendix 1.1
Remote input signals
(1) Warning flag (RX7)
This signal turns on when a minor error occurs.
Five seconds after the cause of the minor error is eliminated, the value in Latest warning code (RWr1) is cleared 
automatically (0000
H
 is stored) and Warning flag (RX7) turns off.
Warning flag (RX7)
Latest warning code (RWr1)
The minor error is
removed.
OFF
ON
ON
OFF
0000
H
Error code or alarm code
Controlled by the D/A converter module
A minor error
occurred.
Remote READY (RXB)
0000
H
5 seconds
5 seconds
have passed.