CHAPTER 3 SPECIFICATIONS
3
3.6  List of Remote 
Register
  
3.6
List of Remote Register
This section lists remote registers for a master/local module.
The remote registers shown are the example with the remote registers of the main module assigned to the remote 
registers of RWr0 to RWrF and RWw0 to RWwF.
Remote register (RWr) is the information input from the D/A converter module to the master/local module.
Remote register (RWw) is the information output from the master/local module to the D/A converter module.
For details on the remote register, refer to the following.
 •
*1
RWrF and RWwF are used by the system in the synchronous communication mode.
Do not read or write the data to/from any "Use prohibited" remote registers. If the data is read or written from/to any of the 
registers, correct operation of the module cannot be guaranteed.
Remote register (RWr)
signal direction: D/A converter module 
Master/local module
Remote register (RWw)
signal direction: Master/local module 
D/A converter module
Device 
number
Description
Device 
number
Description
RWr0
Latest error code
RWw0
Use prohibited
RWr1
Latest warning code
RWw1
Use prohibited
RWr2
CH1 Set value check code
RWw2
CH1 Digital value
RWr3
CH2 Set value check code
RWw3
CH2 Digital value
RWr4
CH3 Set value check code
RWw4
CH3 Digital value
RWr5
CH4 Set value check code
RWw5
CH4 Digital value
RWr6
Use prohibited
RWw6
CH1 Shifting set value
RWr7
Use prohibited
RWw7
CH2 Shifting set value
RWr8
Use prohibited
RWw8
CH3 Shifting set value
RWr9
Use prohibited
RWw9
CH4 Shifting set value
RWrA
Alert output flag
RWwA
Use prohibited
RWrB
Use prohibited
RWwB
Use prohibited
RWrC
Use prohibited
RWwC
Use prohibited
RWrD
Use prohibited
RWwD
Use prohibited
RWrE
Use prohibited
RWwE
Use prohibited
RWrF
*1
Use prohibited
RWwF
*1
Use prohibited