46
6.2
Installation Environment and Installation Position
6.2.1
Installation environment
(1) Installation location
Do not install the D/A converter module to the place where:
 • Ambient temperature is outside the range of 0 to 55°C;
 • Ambient humidity is outside the range of 5 to 95% RH;
 • Condensation occurs due to rapid temperature change;
 • Corrosive gas or combustible gas is present;
 • Conductive powder such as dust and iron powder, oil mist, salinity, or organic solvent is filled;
 • The D/A converter module is exposed to direct sunlight;
 • A strong electric field or strong magnetic field is generated; and
 • The D/A converter module is subject to vibration and shock.
(2) Installation surface
Install the D/A converter module on the flat surface. When the installation surface is uneven, excessive force is 
applied to the printed-circuit board and may cause a defect.
6.2.2
Installation position
When installing the D/A converter module in a control panel, provide clearance of 60mm or longer between the module 
and the sides of control panel or neighboring modules to ensure good ventilation and an easy module change.
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer