Wiring of External Device and Terminal Block
(1) Tightening torque
Tighten the terminal block screws within the following specified torque range.
Failure to secure the terminal block may cause malfunction, failure, or drop.
The following table shows applicable solderless terminals connected to the terminal block. For wiring, use 
applicable wires in the following table and an appropriate tightening torque. Use UL-approved solderless 
terminals. For processing, use a tool recommended by manufacturers of solderless terminals. Sleeved solderless 
terminals cannot be used.
(2) Removing and installing the terminal block
(a) Removal procedure
Screw type
Tightening torque range
Terminal screw (M3 screw)
0.43 to 0.57N•m
Terminal block mounting screw (M3.5 screw)
0.66 to 0.89N•m
Solderless terminal
Wire
Model
Applicable 
tightening torque
Diameter
Type
Material
Temperature 
rating
R1.25-3
0.43 to 0.57N•m
22 to 14 AWG
Stranded
Copper
75°C or more
V2-MS3
RAP2-3SL
TGV2-3N
1.
Open the terminal block cover and loosen the 
terminal block mounting screws (two points).
2.
When the terminal block mounting screws (two 
points) are loosened, the 2-piece terminal block can 
be removed.
Terminal block 