CHAPTER 8 FUNCTION
8
8.5  R
ange Switching F
unction
  
8.5
Range Switching Function
The output range can be selected for each channel from the following ranges:
 • Factory default range (4 to 20mA, 0 to 20mA, 1 to 5V, 0 to 5V, -10 to 10V)
 • User range (user range setting 1, user range setting 2)
(1) Setting procedure
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window 
 Select a D/A converter module in "List of stations". 
 
[CC IE Field Configuration] 
 [Online] 
 [Parameter Processing of Slave Station]
2.
Set "CH D/A conversion enable/disable setting" to "0: Enable".
3.
Set "CH Range setting".
When switching the output range, set Disable (OFF) to CH Output enable/disable flag (RY10 to RY13) before setting a 
value (within the range an external device allows) for CH Digital value (RWw2 to RWw5).
For example, when the output range is from 0 to 5V and 12000 is set for CH Digital value (RWw2 to RWw5), 5V is output. 
In this case, if the output range is changed to -10 to 10V, 7.5V is output because 12000 remains set for CH Digital value 
(RWw2 to RWw5).