Справочник Пользователя для Mitsubishi Electronics LX42C4

Скачать
Страница из 102
42
4.3.4
LY28S1A triac output module (All points independent)
Item
Specifications
Appearance
Number of output points
8 points
Insulation method
Photocoupler isolation
Rated load voltage, 
frequency
100 to 240VAC (+10%/-15%), 50/60Hz(±3Hz)
Maximum load current
1A/point, 8A/module
Load voltage distortion ratio
Within 5%
Maximum load voltage
264VAC
Minimum load 
voltage/current
24VAC/100mA, 100VAC/25mA, 240VAC/25mA
Maximum inrush current
20A/cycle or less
Leakage current at OFF
3mA or lower (at 240V, 60Hz), 1.5mA or lower (at 120V, 60Hz)
Maximum voltage drop at ON
1.5V or lower (at load current of 0.6A)
Response 
time
OFF to ON
Total of 1ms and 0.5 cycles or less
ON to OFF
Total of 1ms and 0.5 cycles or less (rated load, resistive load)
Surge suppressor
CR absorber
Fuse
None (Attaching a fuse to each external wiring is recommended.)
Dielectric withstand voltage
2300VAC, 1 minute (altitude 2000m)
Insulation resistance
10M
 or more by insulation resistance tester
Noise immunity
By noise simulator of 1500Vp-p noise voltage, 1µs noise width and 25 to 60Hz noise 
frequency
Protection degree
IP1X
Common terminal 
arrangement
No common (all points independent)
Number of occupied I/O 
points
16 points (I/O assignment: output 16 points)
External interface
18-point screw terminal block (M3 × 6 screws) (
5VDC internal current 
consumption
200mA (TYP. all points ON)
Weight
0.19kg
Derating chart
60
0
20
40
2
0
8
6
4
Load voltage
3A, 55­
8A, 45­
Ambient temperature (­)
Module 
total output
current
(A)
132VAC/264VAC