Справочник Пользователя для Mitsubishi Electronics QJ7LP25G

Скачать
Страница из 400
 
 
 
4 - 21                                                                                                                                                       4 - 21 
MELSEC-Q
4   SETTING AND PROCEDURE BEFORE OPERATION 
 
4.8 Cable Connections 
4.8.1 Optical loop system 
(1)  Precautions when connecting 
 
(a)  The type of cables that can be used will vary according to the distance 
between stations. 
 
Type 
Interstation distance 
QJ71LP21, 
QJ71LP21-25, 
QJ71LP21S-25, 
QJ72LP25-25 : 
10 Mbps 
QJ71LP21-25, 
QJ71LP21S-25, 
QJ72LP25-25 : 
25 Mbps 
QJ71LP21G 
QJ72LP25G 
QJ71LP21GE 
QJ72LP25GE 
SI optical fiber cable 
(Old type: A-2P-   ) 
L type 
500m (1641 ft.) 
200m (656 ft.) 
Must not be used 
Must not be used 
H type 
300m (984 ft.) 
100m (328 ft.) 
SI optical fiber cable 
500m (1641 ft.) 
200m (656 ft.) 
H-PCF optical fiber cable 
1000m (3281 ft.) 
400m (1312 ft.) 
Broad-band H-PCF optical fiber cable 
1000m (3281 ft.) 
1000m (3281 ft.) 
QSI optical fiber cable 
1000m (3281 ft.) 
1000m (3281 ft.) 
GI-50/125 optical fiber cable 
Must not be used 
Must not be used 
2000m (6562 ft.) 
Must not be used 
GI-62.5/125 optical fiber cable 
Must not be used 
Must not be used 
Must not be used 
2000m (6562 ft.) 
 
(b)  When an optical fiber cable is connected, the following restrictions on the 
bending radius should be observed. 
For details, check the specifications of the cable to be used. 
 
(c)  Maintain the bending radius of the optical fiber cable within the allowable 
range using a tool for securing the optical fiber cable bending radius. 
This tool may be purchased from Mitsubishi Electric System Service, Inc, or 
your nearest dealer. Please inquire for more information. 
 
(d)  When laying the optical fiber cables, do not touch the fiber cores of the cable 
and module connectors, and do not let dust or particles collect on them. 
If oil from hands, dust or particles adhere to the cores, the accumulated 
transmission loss may cause malfunctions in the data link. 
Also, do not remove the cover from the module-side connector until the 
optical fiber cable is ready to be installed. 
 
(e)  When connecting or disconnecting an optical fiber cable, hold the connector 
part of the cable. 
 
(f) 
Connect the cable and module connectors securely until you hear a "click" 
sound. 
 
(g)  Be sure to shut off all phases of the external power supply used in the 
system before connecting or disconnecting optical fiber cables.