Справочник Пользователя для Mitsubishi Electronics QJ7LP25G

Скачать
Страница из 400
 
 
 
4 - 34                                                                                                                                                       4 - 34 
MELSEC-Q
4   SETTING AND PROCEDURE BEFORE OPERATION 
 
4.10.2 Setup confirmation test 
This test checks the switch setting of a network module. 
The following items can be checked. 
1)  Control station overlap status (This check is not performed on remote 
I/O network.) 
2)  Station number duplication status 
3)  Network No. consistency check (Whether the network number set for 
the station where GX Developer is connected matches the network 
number set in network parameter of the host station.) 
 
Station
No. 0
(Parameter settings)
Remote master station
Reserved station Reserved station
Network No. 1
Duplicate error
Station
No. 2
Station
No. 3
Station
No. 4
Station
No. 1
Station
No. 7
Station
No. 1
Station
No. 5
Duplicate error
GX Developer
 
When the setup confirmation test is performed using GX Developer connected to the 
remote master station in the system above, the following screen appears. 
The result shows that the station number 1 has a station No. duplication error.