MELSEC-Q
5   PARAMETER SETTINGS 
 
5.1 Remote Master Station Parameter Setting 
The remote master station sets the network parameters to the CPU module. 
 
5.1.1 Setting the number of modules (Network type) 
Set the network type and the station type for each module. 
No. of mountable modules is the maximum number of mountable network modules 
with CC-Link IE Controller Network. 
Note, however, that there are restrictions on the number of network modules that can 
be mounted, depending on the CPU module used. (Refer to Section 2.5.) 
Select the remote master station for the MELSECNET/H network system. 
 
 
 
(1) Selection 
type 
Select the following item. 
•  MNET/H (Remote master): 
When the remote master station is 
specified 
•  MNET/H (Multiplexed remote master): 
When the multiplexed remote 
master station is specified 
•  MNET/H (Multiplexed remote sub-master):   When the multiplexed remote sub-
master station is specified 
 
(2) Precautions 
 
(a)  If a QnA/A series MELSECNET/10 network module is erroneously 
connected to a MELSECNET/H remote I/O network, the network system 
will operate as follows. 
•  If the remote master station is a MELSECNET/H network module, 
MELSECNET/10 network modules on remote I/O stations will be 
disconnected from the network. 
•  If the remote master station is a MELSECNET/10 network module, 
MELSECNET/H network modules on remote I/O stations will be 
disconnected from the network.