Справочник Пользователя для Mitsubishi Electronics QJ7LP25G

Скачать
Страница из 400
 
 
 
3 - 4                                                                                                                                                                                3 - 4 
MELSEC-Q
3   SPECIFICATIONS 
 
3.1.3 Optical fiber cable specifications 
This section explains the specifications of the optical fiber cables used with the 
MELSECNET/H optical loop system. Confirm that the cable in use conforms to the 
details of the optical fiber cable specifications. 
A technical skill and a special tool are needed when connecting an optical fiber cable 
to an exclusive connector. 
Optical fiber cables with connectors are also available. 
For cabling, please consult your local Mitsubishi representative. 
 
Table 3.3    Optical fiber cable specifications 
Item 
SI (Multi-
particulate glass) 
H-PCF (Plastic-
clad) 
Broad-band H-
PCF (Plastic-clad)
QSI (Quartz 
glass) 
QI-50/125 (Quartz 
glass) 
QI-62.5/125 
(Quartz glass) 
Interstation 
distance 
10 Mbps 
500 m 
1 km 
1 km 
1 km 
2 km 
2 km 
25 Mbps 
200 m 
400 m 
1 km 
1 km 
Must not be used  Must not be used
Transmission loss 
12 dB/km 
6 dB/km 
5 dB/km 
5.5 dB/km 
3 dB/km 
3 dB/km 
Core diameter 
200 
 m 
200 
 m 
200 
 m 
185 
 m 
50 
 m 
62.5 
 m 
Clad diameter 
220 
 m 
250 
 m 
250 
 m 
230 
 m 
125 
 m 
125 
 m 
Primary membrane 
250 
 
m — 
— 250 
 m 
— 
— 
Applicable connector 
F06/F08 or equivalent (JIS C5975/5977 conformance) 
 
REMARKS 
The following types of optical fiber cables are available. 
A type: Cable for connection inside control panel 
B type: Cable for connection between control panels inside a building 
C type: Cable for outdoor connection 
D type: Reinforced cable for outdoor connection 
For other special-purpose cables such as flexible cables or heat-resistant cables, 
please contact your local Mitsubishi representative. 
 
(1)  Cable loss of GI-62.5/125 optical fiber cable 
 
Optical
module
IN
OUT
SD
RD
SD
RD
QJ71LP21GE
QJ72LP25GE
Conversion cable (1m) *1
Adaptor
Connection loss: 1 dB (max.)
Connection loss: 1 dB (max.)
Adaptor
Conversion cable (1m) 
SD
RD
SD
RD
IN
OUT
Total cable loss = 7.5 dB or less
5.5 dB or less
 
 
1: Conversion cable 
Conversion Type 
Cable 
CA type 
 FC type 
AGE-1P-CA/FC1.5M-A 
CA type 
 ST type 
AGE-1P-CA/ST1.5M-A 
CA type 
 SMA type 
AGE-1P-CA/SMA1.5M-A 
Purchased from: Mitsubishi Electric Europe GmbH