3 - 60                                                                                                                                                                                3 - 60 
MELSEC-Q
3   SPECIFICATIONS 
 
3.3.4 Output holding time during system switching in the multiplexed remote I/O network for 
redundant system 
In the multiplexed remote I/O network for redundant system, if an error occurs in the 
multiplexed remote master station of the control system, the multiplexed remote sub-
master station of the standby system takes over the control of remote I/O stations.    At 
the time of system switching, remote I/O stations hold the outputs (data). 
The output holding time of remote I/O stations during system switching differs with the 
reason of system switching.    In addition, it is affected by the CPU system switching 
time and the switching time between a multiplexed remote master station and a 
multiplexed remote sub-master station. 
The following shows the calculation formula of output holding time for each reason for 
system switching. 
 
(1)  When a power failure or CPU module stop error occurs 
 
 
 
(a)  CPU system switching time < System switching time from the multiplexed 
remote master station to the multiplexed remote sub-master station 
 
Standby system     control system CPU
Output holding time of remote I/O station
A power failure has occurred on the control system
SS
Ds2
Toh
Control system     standby system CPU
 
 
[Output holding time (Toh)]
Toh = Ds2 + SS [ms]
 
 
Ds2: Switching time from the multiplexed remote master station to the 
multiplexed remote sub-master station [ms] 
SS:  Scanning time of the redundant CPU [ms]