4 - 2                                                                                                                                                       4 - 2 
MELSEC-Q
4   SETTING AND PROCEDURE BEFORE OPERATION 
 
4.2 Part Names and Settings 
4.2.1 QJ71LP21, QJ71LP21-25, QJ71LP21S-25, QJ71LP21G, QJ71LP21GE, QJ71BR11 
(Remote master station) 
(1)   QJ71LP21, QJ71LP21-25, QJ71LP21S-25, QJ71LP21G, 
QJ71LP21GE 
 
 
 
(a) LED 
indications 
 
No. Name LED 
status 
Description 
1 RUN 
ON 
(green) 
Normal operation 
   OFF 
Watchdog timer error (hardware failure) 
MNG
1
 
ON (green)  Operating as a remote master station 
   OFF 
Not operating as a remote master station 
3 T.PASS 
ON 
(green) 
In the baton pass status (The module is connected to the network.) 
 
 
Flashing 
(green) 
Being tested (When the LED flashes 20 times or more (approx. 10 seconds), it means the end of 
the test.) 
   OFF 
Not in the baton pass status (The host station has been disconnected from the network.) 
4 D.LINK 
ON 
(green) 
Data link being performed (Cyclic transmission is being performed.) 
 
 
OFF 
Data link not being performed (Parameters have not been received, an error has occurred in the 
CPU module of host station, a data link stop instruction has been issued, or others.) 
5 SD 
ON 
(green) 
Data being sent 
   OFF 
Data not being sent 
6 RD 
ON 
(green) 
Data being received 
   OFF 
Data not being received 
1: The LED of the sub-master operating station in a multiplexed remote I/O network is off.
 
 
 
 
 
 
 
 4