5   PARAMETER SETTINGS 
 
5.1.2 Network settings 
These parameters are used to configure the MELSECNET/H network. 
Set the starting I/O No., network No., total number of (slave) stations, group No. and 
mode for each of the module model names set in the number of modules settings. 
 
(1)  Starting I/O No. 
Set the start I/O No. to which the module is loaded in 16-point units in 
hexadecimal for each applicable network module. 
For example, set 130 when the network module is loaded onto X/Y130 to 14F. 
 
Q61P
QCPU QX42 QX42 QX41 QY41 QY41
QJ71
QY41
64 pts 64 pts 32 pts 32 pts 32 pts 32 pts
32 pts
48 pts
Empty
X/Y
00
H
 to
3F
H
40
H
to 
7F
H
80
H
to 
9F
H
A0
H
to 
BF
H
C0
H
to 
DF
H
E0
H
to 
FF
H
100
H
 to
12F
H
130
H
 to
14F
H
 
 
(a)  Valid setting range 
0
H
 to 0FE0
H
 
 
(b) Precaution 
Unlike the setting method for the AnUCPU (where the higher two digits of 
the 3-digit value should be set), here all three digits should be set as is. 
 
(2) Network 
No. 
Set the network number to which the applicable network module is connected. 
 
(a)  Valid setting range 
1 to 239 
 
(3) Total 
stations 
Set up the total number of multiplexed remote sub-master stations, remote I/O 
stations, and reserved stations in a single network. 
 
CPU QJ71
1M
R
Remote master station
QJ72
I/O
1R1
QJ72
1R2
Network No.1
QJ72
1R3
Total stations 3
I/O
Reserved
stations
 
 
(a)  Valid setting range 
1 to 64