Справочник Пользователя для Mitsubishi Electronics QJ71LP21

Скачать
Страница из 400
 
 
 
5 - 15                                                                                                                                                       5 - 15 
MELSEC-Q
5   PARAMETER SETTINGS 
 
5.1.4 Supplementary settings 
The supplemental settings are included in common parameter settings to provide more 
precise usage. Keep the default settings for normal use. 
Common parameters supplemental are only for remote master stations. 
 
1)
2)
3)
4)
5)
6)
7)
 
 
[Setting items] 
1) Constant 
scan 
The constant link scan function is used to maintain the link scan time 
constant. 
If the response time is long for the transient transmission function, 
setting the constant link scan function may reduce the response time. 
Set a value in the following range to use a link scan time:  
 
Setting time 
Constant link scan 
Blank 
Not executed (default) 
1 to 500 ms 
Executed using the set time