7   APPLICATION FUNCTIONS 
 
7.3 Device Test for Remote I/O Station 
The remote I/O network can use operations of GX Developer connected to the remote 
I/O station to test the input/output devices of the sequence program without affecting 
the online system.     
To conduct a test without affecting the system, register the device to be tested in 
"Forced input output registration/cancellation" in "debug" in the online menu.    For 
details about operating the GX Developer, refer to the operating manual for GX 
Developer. 
 
The test is performed on the following items. 
 
(1)  Stops the Y output from the remote master station to the remote 
I/O station. 
Even when the Y output is set to ON on the sequence program, it is not output 
from the remote I/O station, allowing output testing of the sequence program to 
be tested safely.    Moreover, if GX Developer is connected directly to the remote 
I/O module, forced output from GX Developer to the remote I/O module can be 
performed. 
At this time, the X input from the remote I/O station is input to the remote master 
station. 
 
Common parameters
 
 
QCPU
Remote master station
Remote I/O 
station No. 1
GX Developer
Forced output Y
LX
LY
LX
LY
GX Developer
Forced output for station
number No.1 Y1020
LY is not output
to station No.1
Remote I/O 
station No. 2