7   APPLICATION FUNCTIONS 
 
7.8 I/O Assignment Function 
Master Remote 
 
 
 
The I/O assignment function is used for the following: 
1) Reserving points when changing to a module other than 16-point modules 
2) Preventing I/O number change after module replacement 
3) Changing I/O numbers to those used in the program 
4) Setting input response time (I/O response time) 
5) Setting an output mode for a data link error (Error time output mode setting) 
6) Setting a remote I/O station operation mode for a hardware error in an intelligent 
function module (Hardware error time CPU operation mode setting) 
7) Setting intelligent function module switches 
 
To enable the I/O assignment functions, use GX Developer to set the I/O assignment 
settings in the PLC parameters for the remote I/O station.    The I/O assignments are 
set within common parameter setting range that has been set in remote master station. 
As for the I/O assignment settings in the PLC parameters of the remote master station, 
the I/O assignment within the remote master station are enabled but they are not 
enabled in the remote I/O station. 
Moreover, the I/O assignment of the remote I/O station is only set for remote I/O 
stations requiring I/O assignment.    There is no need to set for all remote I/O stations. 
 
(GX Developer I/O assignment setting screen) 
 
 
 
For details about the concepts relating to input/output number assignment and for 
details about using GX Developer for I/O assignment, refer to the user's manual 
(Function Explanation, Program Fundamentals) of the CPU module used.