Справочник Пользователя для Mitsubishi Electronics QJ71LP21

Скачать
Страница из 400
 
 
 
7 - 39                                                                                                                                                                                                          7 - 39 
MELSEC-Q
7   APPLICATION FUNCTIONS 
 
7.11.4 Access function by specifying the control system or standby system 
This function is for making access to the Redundant system by specifying the control 
system or standby system using GX Developer or other methods. By using this 
function, access to the control system is enabled even after system switching occurs 
due to error. 
 
Power 
supply
QnPRHCPU QJ71
LP21
Link cable
Tracking cable
Power 
supply
QJ71
E71
Power 
supply
QnPRHCPU QJ71
LP21
QJ72
LP25
GX Developer
QnPRHCPU can be accessed by specifying either the control system or standby system
Control system
Standby system
System A
System B
 
 
The settings on the request source (GX Developer) are as follows. 
Specify the control system, standby system, system A, or system B on the connection 
setup screen in the online menu. 
 
Specify the control system, 
standby system, system A, 
or system B.
 
 
REMARKS 
For the details of the GX Developer operation, refer to the operation manual of GX 
Developer.