8 - 52                                                                                                                                                         8 - 52 
MELSEC-Q
8   TROUBLESHOOTING 
 
8.4  Canceling a Minor Error (Continue Error) on a Remote I/O Station 
An error of a remote I/O module can be canceled if it is a type of errors that allows the 
module operation to continue, as in the case of CPU modules. 
The following explains errors that can be canceled and how to cancel them. 
 
(1)  Errors that can be canceled 
The errors listed below can be canceled. 
For error details, refer to Section 8.3.3. 
 
Error code 
Error message 
1300 
FUSE BREAK OFF 
1
 
1401 
SP. UNIT DOWN 
1
 
1403 
SP. UNIT DOWN 
1
 
1510 
SINGLE PS. DOWN 
1520 
SINGLE PS. ERROR 
2000 
UNIT VERIFY ERR. 
1
 
1: Can be canceled only when “Continue” is set in the CPU module on the remote 
master station and in PLC parameter (Error time operation mode, H/W error time 
CPU operation mode) for the remote I/O station. 
If “Stop” has been selected, the error cannot be canceled because it is regarded 
as a moderate error (stop error). 
 
(2)  How to cancel an error 
The following lists how to cancel an error. 
 
Item Operation 
Availability 
Reference 
section 
GX 
Developer 
Sequence 
program 
Canceling a specific 
remote I/O station error 
Manipulate the remote master station and a remote 
I/O station to cancel only a specific remote I/O station 
error. 
 
 
8.4.1 
Canceling errors of all 
remote I/O stations 
Manipulate the remote master station to cancel errors 
of all remote I/O stations. 
 
 
8.4.2 
: Available 