Справочник Пользователя для Mitsubishi Electronics QJ71LP21

Скачать
Страница из 400
 
 
 
2 - 12                                                                                                                                                             2 - 12 
MELSEC-Q
2   SYSTEM CONFIGURATION 
 
(2)  Table 2.8 lists the setting items for the remote I/O module main module for the 
remote I/O station (R) and the parameter setting items from the GX Developer. 
 
Table 2.8 Remote I/O station setting items 
Setting items 
Remote I/O station (R) 
Reference 
Network module main module switch 
 
STATION NO. 
1 to 64 
Section 4.2.2 
 MODE 
 
Section 4.2.2 
GX Developer parameter setting 
 PLC 
system 
 
 PLC 
RAS 
 
 I/O 
assignment 
 Operation 
setting 
Section 5.2.1 
 Ethernet 
setting 
 CC-Link 
setting 
 
Remote password setting 
 
Section 7.12 
GX Configurator setting 
 Initial 
setting 
 
Section 5.2.1(4)
 
Auto refresh setting 
 
Section 5.2.1(4)
: Always set,  : Default setting,  : Set as needed,  : No need to set 
 
4 : Refer to the User's Manual (Function Explanation, Program Fundamentals) for 
the CPU module used. 
5 : Refer to the Q Corresponding Ethernet Interface Module User's Manual (Basic) 
(SH-080009). Note that the interrupt setting is not available. 
6 : Refer to the MELSEC-Q CC-Link System Master/Local Module User's Manual 
(SH-080394E). Note that the interrupt setting is not available. 
 
2.4.3 Available device ranges 
The remote I/O network can use the following device ranges in the network module. 
 
Device Available 
range 
Others 
LB 0
H
 to 3FFF
H
 (16384 points)
— 
LW 0
H
 to 3FFF
H
 (16384 points)
LX 0
H
 to 1FFF
H
 (8192 points)  The device range (excluding that of I/O module mounted on the host 
station) should be assigned to each network module. 
LY 0
H
 to 1FFF
H
 (8192 points) 
 
B/W
LB/LW
Remote I/O network 2
LB/LW
CPU module
0
3FFF
H
2000
H
3000
H
(4096)
1000
H
(8192)
(12288)
(16383)
Remote I/O network 1
X/Y
LX/LY
Remote I/O network 2
LX/LY
CPU module
Remote I/O network 1
Real I/O
1: Expandable by changing from [PLC parameters] - [Device settings]
Extended function area    1