(d)  Cyclic transmission delay 
Since Sm = 1 [ms],LS = 11.8 [ms], the Sm < LS formula is used. 
 
1)  Input transmission delay time (T
DX
)] 
T
DX
 = (Sm + 
m)    round up [LS/(Sm + m)]    2 + Sm + T
RIOR
 
= (1 + 0.41)    [11.8/(1 + 0.41)]    2 + 1 + 0.024 
= 24.6 [ms] 
 
2)  Output transmission delay time (T
DY
)] 
T
DY
 = (Sm + 
m)    round up [LS/(Sm + m)] + LS + T
RIOR
 
= (1 + 0.41)    [11.8/(1 + 0.41)] + 11.8 + 0.024 
= 23.6 [ms] 
 
3.3.3 Switching time from the multiplexed remote master station to the multiplexed remote 
sub-master station in a multiplexed remote I/O network 
In the multiplexed remote I/O network system, the multiplexed remote sub-master 
station takes over the control of the remote I/O station from of the multiplexed remote 
master station when it develops an error. 
While control is switched from the multiplexed remote master station to the multiplexed 
remote sub-master station, the remote I/O station holds output (data). 
The switching time from the multiplexed remote master station to the multiplexed 
remote sub-master station is expressed with the formula below: 
 
Network
Multiplexed remote 
sub-master station
Switching time
An error has occurred on the multiplexed remote master station
K1
Cs
Cm
K2
Ds2
 
 
[Switching time from the multiplexed remote master station to the multiplexed 
remote sub-master station (Ds2)]
Ds2 = K1 + Cs + Cm [ms]
 
 
K1: Internal processing time 
•  When a power failure or CPU module stop error occurs: 620ms 
•  When a system is switched by the following: execution of a system switching 
instruction, a system switching request by GX Developer, or link cable 
disconnection on other network modules: 160ms 
Cs: Normal station baton passing/cyclic communication initializing time   
= Number of normal stations   9 [ms] 
Cm: Error station baton passing/cyclic communication initializing time   
= Number of error stations   16 [ms] 