Справочник Пользователя для Mitsubishi Electronics QJ71LP21S-25

Скачать
Страница из 400
 
 
 
4 - 6                                                                                                                                                       4 - 6 
MELSEC-Q
4   SETTING AND PROCEDURE BEFORE OPERATION 
 
4.2.2 QJ72LP25-25, QJ72LP25G, QJ72LP25GE, QJ72BR15 
(1)  QJ72LP25-25, QJ72LP25G, QJ72LP25GE 
 
 
 
(a) LED 
indications 
 
No. Name LED 
status 
Description 
1 RUN 
ON 
(green) 
Normal operation 
   OFF 
Watchdog timer error (hardware failure) 
REM. 
1
 
ON (green)  Normal operation 
  Flashing 
(green) 
Parameters being written to the flash ROM or in device test mode 
   OFF 
Being initialized remotely or error (watchdog timer error, fuse blown error, I/O module verify error, 
or other errors) 
3 T.PASS 
ON 
(green) 
In the baton pass status (The module is connected to the network.) 
  Flashing 
(green) 
Being tested (When the LED flashes 20 times or more (approx. 10 seconds), it means the end of 
the test.) 
   OFF 
Not in the baton pass status (The host station has been disconnected from the network.) 
4 D.LINK 
ON 
(green) 
Data link being performed (Cyclic transmission is being performed.) 
   OFF 
Data link not being performed (Parameters have not been received, an error has occurred in the 
CPU module of host station, a data link stop instruction has been issued, or others.) 
5 SD 
ON 
(green) 
Data being sent 
   OFF 
Data not being sent 
6 RD 
ON 
(green) 
Data being received 
   OFF 
Data not being received