6 - 1                                                                                                                                                                 6 - 1 
MELSEC-Q
6   PROGRAMMING 
 
6 PROGRAMMING 
When diverting the program example introduced in this chapter to the actual system, 
fully check that there are no problems in the controllability of the system. 
 
6.1 Programming Precautions  
This section explains the precautions in creating programs using data on the network. 
 
6.1.1 Interlock related signals 
A list of the interlock signal devices used in the sequence programs is provided below. 
Refer to Appendix 2, "List of the Link Special Relays (SB)" and Appendix 3, "List of the 
Link Special Registers (SW)" for other explanations, such as the operation status and 
setting status of the host and other stations. 
When multiple network modules are installed, the interlock signal devices are 
refreshed to the devices on the PLC side at 512 points (0
H
 to 1FF
H
) intervals according 
to the default settings as listed below. 
 
POINT 
 
The Q series uses the link special relays (SB) and the link special registers (SW) in 
the entire intelligent function module. Therefore, do not use the same SB and SW 
more than once in a program. 
 
Assignment of the link special relay (SB) and the link special register 
(SW) when multiple modules are installed 
Mounting 
position
Device 
1st module 
2nd module 
3rd module 
4th module 
SB 0
H
 to 1FF
H
 200
H
 to 3FF
H
 400
H
 to 5FF
H
 600
H
 to 7FF
H
 
SW 0
H
 to 1FF
H
 200
H
 to 3FF
H
 400
H
 to 5FF
H
 600
H
 to 7FF
H
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 6