8   TROUBLESHOOTING 
 
8.2.9 Checking incorrect optical fiber cable connection during online 
This section explains the checking procedure for incorrect optical fiber cable 
connection (IN-IN, OUT-OUT) during online and the link special registers (SW009C to 
SW009F) used for the check. 
Unlike the loop test, the checking procedure given in this section allows a check 
without stopping a data link. 
If incorrect cable connection is found, correct the wiring after shutting off all phases of 
the system. 
 
POINT 
 
Before starting the check given in this section, make sure that the following 
conditions are satisfied. 
If these are not satisfied, conduct a loop test to make a check. 
Multiplex transmission function is not used. 
The optical fiber cables have no breaks. (Both the forward and reverse loop 
cables are normal.) 
There are no stations having data link error (power off, MELSECNET/H module 
failure).