App - 1                                                                                                                                                     App - 1 
MELSEC-Q
APPENDICES 
 
APPENDICES 
Appendix 1 Precautions for Replacing MELSECNET/10 Remote I/O Network with 
MELSECNET/H Remote I/O Network 
This section describes the precautions for replacing MELSECNET/10 remote I/O 
network for the AnUCPU and QnACPU with MELSECNET/H remote I/O network for 
the QCPU. 
 
(1)  Use of only one type of network module 
MELSECNET/H network modules and MELSECNET/10 network modules 
cannot be used together in a system. 
Use only MELSECNET/H remote I/O modules. 
Note that if a MELSECNET/H remote I/O module is set in MELSECNET/10 
mode, the module is used as a MELSECNET/10 remote I/O station. 
 
(2) Switch settings 
The network number setting switches and condition setting switches of 
MELSECNET/10 network modules do not exist on MELSECNET/H network 
modules. 
Configure these settings in network parameters. 
 
(3)  Correction of remote master station network parameters 
The network parameters for the remote master station require the corrections 
described in (2) above. 
 
(4)  Setting of parameters to remote I/O station  
•  The I/O assignment settings set by the network parameters of the 
MELSECNET/10 remote I/O network master module is set by the remote I/O 
module PLC parameters on the MELSECNET/H remote I/O network. 
•  When changing the intelligent function modules mounted to the remote I/O 
station, there is a need to make switch settings using the remote I/O station 
PLC parameters.  For details, refer to the user's manual for the intelligent 
function module being used. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 A