2 - 15                                                                                                                                                             2 - 15 
MELSEC-Q
2   SYSTEM CONFIGURATION 
 
2.5.2 Applicable systems for remote I/O stations 
This section explains application systems of remote I/O stations. 
Mount a remote I/O module to a CPU slot of any of the main base units. 
 
(1)  Applicable main base units, power supply modules and No. of 
modules 
 
Main base unit
*1
 
Power supply module 
Number of mountable 
remote I/O modules
*2
 
Q33B, Q35B, Q38B, Q312B 
Q6 P 
1 (mounted in the CPU 
slot) 
Q35BL, Q38BL 
(Q series large type main base 
unit) 
Q6 P 
Q35BLS, Q35BLS-D, Q38BLS, 
Q38BLS-D 
(AnS size Q series large type main 
base unit) 
Q6 P 
Q32SB, Q33SB, Q35SB 
(Slim type main base unit) 
Q61SP 
Q35DB, Q38DB, Q312DB 
(Multiple CPU high-speed main 
base unit) 
Q6 P 
Q38RB 
(Main base unit for the redundant 
power supply system) 
Q63RP, Q64RP 
*1:  Total of up to 64 modules can be mounted to a base unit. Mount a module 
within the number of I/O points for the remote I/O module. If the number of 
slots is within the available range, the module can be mounted on any slot. 
*2:  Depending on the combination with other modules or the number of 
mounted modules, power supply capacity may be insufficient. 
Pay attention to the power supply capacity before mounting modules, and if 
the power supply capacity is insufficient, change the combination of the 
modules.