MELSEC-Q
3   SPECIFICATIONS 
 
3.2.1 Cyclic transmission function (periodic communication) 
The cyclic transmission function periodically exchanges data between the remote 
master station and remote I/O station using link device (LX/LY/LB/LW)   
The following explains the differences between when the module connected to the 
remote I/O station is an I/O module and when it is an intelligent module connected to it. 
 
(1)  Communicating with I/O modules 
The remote master station uses input/output X/Y(LX/LY) devices after the actual 
I/O for the host so that there can be communication with the I/O module on the 
remote I/O station. 
To perform communications between the remote master station and the remote 
I/O station, write the network parameters to the remote master station. 
The device range for communicating with each remote I/O station is set by the 
remote master station common parameters. 
PLC parameters written to the remote I/O station will not cause problems with the 
I/O module communication, even with the default settings. Change the settings of 
the PLC parameters as needed. 
 
Actual I/O
X
Y
0
1000
100F
1010
101F
1FFF
LX
LY
0
1000
100F
1010
101F
1FFF
Y1010
X1000
QCPU
Master module
Remote master station
1)
LX
LY
0
0F
10
1F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
X
Y
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
2)
Remote I/O station
Remote I/O module
Input module
Output module
to
to
to
to
to
to
 
 
1)  When X0 for the input module for the remote I/O station is set to on, 
the X1000 for the remote I/O station is set to on. 
 
2)  When Y1010 for the remote master station is set to on, the Y10 for the 
remote I/O station output module is set to on.