SE TO INCREASE THE POWER ON AN EXISTING INSTALLATION
 
Description: 
The availability of an inverter or a inverter/charger 
allows its power to be extended with an Xtender 
connected in cascade. The maximum power of 
the first inverter is limited by the maximum current 
from the transfer relay of the Xtender. 
 
 
Associated current configurations: 
•  Maximum current of the AC source {1107} Adjust this configuration in relation to the maximum 
current that can supply the old inverter. 
•  Locking: Smart boost inactive {1126} Suppress the locking of this function: This way, when the first 
inverter has reached it maximum power, the power consumed that will be supplied by the 
Xtender could be increased. 
•  Locking: Inactive charger {1125} This lock, without which the battery energy would be taken by 
the first inverter, is returned by the Xtender charger. This would only have the effect of 
discharging the battery with losses caused in the two inverters or inverter/chargers. 
L
OAD SHEDDING OF THE SECOND PRIORITY LOADS
 
Description: 
Consumers with different supply priorities allow 
automatic disconnection of the supply to 
consumers of lower priority if the battery becomes 
weak. The supply of the priority loads is thus 
assured, such as lighting or computers, for 
example. In this case, the low-priority loads must 
be cabled via one of the auxiliary relays. The 
reference for the example below correspond to 
the auxiliary contact no 1. 
 
 
Associated current configurations: 
•  Communication mode {1202} 
•  Relay activated by the battery voltage {1245} 
•  Voltage 1 active {1246} 
•  Voltage 1 {1247} 
•  Duration 1 active {1248} 
•  Voltage for deactivation of the auxiliary relay {1255} 
•  Duration for deactivation {1256}