Creating and Running Algorithms 203
To set up the algorithms for this example:
1. Define the global variable <cold_setpoint>.
ALG:DEF 'GLOBALS','static float cold_setpoint;'
2. Define the following algorithm language code as ALG1, the ratio
station algorithm.
static float hot_flow, cold_hot_ratio;
static float cold_temp = 55, hot_temp = 180, product_temp = 120;
hot_flow = I108;
static float cold_temp = 55, hot_temp = 180, product_temp = 120;
hot_flow = I108;
/* get flow rate of cold supply */
/* following line calculates cold to hot ratio from supply and product temps */
cold_hot_ratio = (hot_temp - product_temp) / (cold_temp - product_temp);
cold_setpoint = hot_flow * cold_hot_ratio; /* output flow setpoint for ALG2 */
cold_hot_ratio = (hot_temp - product_temp) / (cold_temp - product_temp);
cold_setpoint = hot_flow * cold_hot_ratio; /* output flow setpoint for ALG2 */
3. Modify a PIDA algorithm so its setpoint variable is the global
variable cold_setpoint, its input channel is I109 and its output channel
is O116 and Define as ALG2, the cold supply flow controller.
is O116 and Define as ALG2, the cold supply flow controller.
/* Modified PIDA Algorithm; comments stripped out, setpoint from global,
inchan = I109, outchan = O116
*/
/* the setpoint is not declared so it will be global */
inchan = I109, outchan = O116
*/
/* the setpoint is not declared so it will be global */
static float P_factor = 1;
static float I_factor = 0;
static float D_factor = 0;
static float I_out;
static float Error;
static float Error_old;
static float D_factor = 0;
static float I_out;
static float Error;
static float Error_old;
FT
flow transmitter
ALG2
Flow Controller
Flow Controller
ALG1
Ratio Station
Ratio Station
flow transmitter
FC
55
°
Cold Supply
GLOBAL
cold_setpoint
I108
O116
I109
180
°
Hot Supply
120
°
Product
Figure 6-4. Inter-algorithm Communication with Globals
FT
RS