Справочник Пользователя для Siemens LR 460
7ML19985JM01
SITRANS LR 460 – INSTRUCTION MANUAL
Page 41
mmmmm
S
IMA
T
IC PD
M.
2.
You will need the most up-to-date Device Description (DD) for your instrument.
Launch SIMATIC PDM – Manager Device Catalog, browse to the unzipped DD file
and select it.
and select it.
3.
Launch SIMATIC Manager and create a new project for LR 460. Application Guides
for setting up HART and PROFIBUS PA devices with SIMATIC PDM.can be
downloaded from the product page of our website at:
https://pia.khe.siemens.com/index.asp?Nr=14655
downloaded from the product page of our website at:
https://pia.khe.siemens.com/index.asp?Nr=14655
4.
Open the Menu Device – Reset and click on Factory Reset.
5.
Upload parameters to the PC/PG.
6.
Calibrate the device.
Calibrating LR 460 via PDM
•
See
on page 30 and follow 4 steps to setup
for a simple application.
•
Open the menu Device – Sensor Calibration to set parameters individually.
•
For a complete list of parameters see
Parameters accessed via pull-down menus
See
on page 43 for a complete list of parameters
that can be accessed only via pull-down menus in SIMATIC PDM.
Reset
Factory Defaults
Use Factory Defaults to reset all parameters excluding device addresses to the default
settings.
settings.
1. Open the menu Device – Reset, select Factory Defaults, and click OK.
2. After the reset is complete upload parameters to the PC/PG.
2. After the reset is complete upload parameters to the PC/PG.
Device Reset
This has the same effect as cycling power (a Warm Start). It does not reset any
parameters.
parameters.
• Open the menu Device – Reset, select Device Reset, and click OK to the option
Master Reset?
Configuration Flag Reset (HART only)
To reset the configuration flag to zero, open the menu Device – Configuration Flag Reset
and execute a reset.
and execute a reset.
Auto False Echo Suppression
Use this parameter to learn a new TVT curve, to avoid false echoes caused by
obstructions. See
obstructions. See
on page 73 for a more detailed
explanation and
on page 57 for instructions.