13 - 1 
 
 
 
 
 
13 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
13. ALARM NUMBER 
 
13. ALARM NUMBER 
The position board can raise the following four alarms: system alarm, servo alarm, operation alarm, and 
system error. The alarm numbers are represented in hexadecimal numbers. 
 
API LIBRARY  
Use the sscGetAlarm/sscResetAlarm functions to get/reset the alarm number. 
Specify the following in the argument for the alarm type. 
System alarm    :  SSC_ALARM_SYSTEM 
Servo alarm      : SSC_ALARM_SERVO 
Operation alarm: SSC_ALARM_OPERATION 
 
 
13.1 System alarm 
Alarm 
No. 
Content 
Detail 
No. 
Cause of occurrence 
Procedure 
35 
Operation cycle 
alarm 
01 
An operation cycle alarm 
occurred. 
Reexamine the following. 
(1) Make the control cycle setting longer. 
(Example. When control cycle is 0.44ms, change 
to 0.88ms) 
(2) Decrease the number of control axes. 
(3) Reexamine the operation pattern so that the 
timing of the operation startup of each axis does 
not overlap. 
36 
Number of write 
accesses to flash 
ROM error 
01 
The number of write accesses to 
flash ROM by parameter 
backups exceeds 100,000 times.
Data cannot be written to the flash ROM because the 
flash ROM is expected to reach its service life. 
03 
The number of write accesses to 
flash ROM by parameter 
backups exceeds 25 times after 
system preparation completion.
Check for unnecessary parameter backups. To 
perform the parameter backup again, reset the 
system alarm. 
37 
(Note) 
Parameter error 
01 
Parameter setting is erroneous.
Set the setting to a correct value within the parameter 
limits. 
3B 
(Note) 
Mark detection 
setting error 
01 
When mark detection is enabled, 
the total number of continuous 
latch data storages (parameter 
No.02B0, No.02B2) for the whole 
system exceeds 64. 
Set the total number of continuous latch data 
storages (parameter No.02B0, No.02B2) for the 
whole system to within 64. 
 
Note. The system alarm cannot be reset.