6 - 1 
 
 
 
 
 
 
 
 
 
 
 
 6
 
 
 
 
 
 
 
 
 
 
 
6. APPLICATION FUNCTIONS 
 
6. APPLICATION FUNCTIONS 
6.1 Command units 
6.1.1 Position command unit - electronic gear 
Set position command (such as position data of point table and the incremental movement amount) by position 
command unit. Electronic gears (parameter No.020A, 020B, 020C, 020D) are used to adjust position 
command unit. Through making changes to the electronic gears, it is possible to move the equipment using an 
arbitrary multiplication constant for the movement amount. 
 
 
Electronic gear = 
Electronic gear numerator (CMX)
 Electronic gear denomnator (CDV)  
 
 
The number of encoder pulses per revolution is 4194304 or less (normal servo motor, linear servo motor etc.).  
 
Item Setting 
range 
Number of encoder pulses 
per revolution [pulse] (Note 1)
Maximum speed [r/min] (Note 2,3) 
Electronic 
gear 
CMX 
1 CMX 5242879 
(When the speed unit is position 
command unit/s or position 
command unit/min) 
To 67108864 
(The resolution of up to 26 bit 
is supported.) 
Limits the speed to 2160000   
(262144/number of encoder pulses 
per revolution)   (CMX/CDV) or less, 
and to 4893355   (262144/number of 
encoder pulses per revolution) or less
1 CMX 477218 
(When the speed unit is r/min) 
CDV 1 CDV 589823 
CMX/CDV 1/16 CMX/CDV 100000 
Note 1. When a linear servo motor is used, this becomes the value which is set in "Stop interval setting for home position return" of the 
linear/direct drive motor function selection 1 (parameter No.1300). 
         2. When the command speed output to the servo amplifier from the position board exceeds the motor maximum revolution speed, 
the speed is limited to the motor maximum revolution speed (monitor No.0114). 
         3. When a linear servo motor is used, this is converted into maximum speed [r/min] by the following formula. 
 
Maximum speed [r/min] = 
Motor maximum speed[m/s]×1000×1000×60
Linear encoder resolution[μm/pulse]×Stop interval setting for home position return[pulse]  
 
However,  
Linear encoder resolution [µm/pulse] = 
Linear encoder resolution setting Numerator (Parameter No.1301)
Linear encoder resolution setting Denominator (Parameter No.1302)]  
 
 
API LIBRARY  
Use the sscChange2Parameter/sscCheck2Parameter functions to set/get 
electronic gear.