6 - 20 
6. APPLICATION FUNCTIONS 
 
6.10 Interlock 
When the interlock signal (ITL) is turned on, movement is temporarily stopped. During stoppage of movement 
the interlock stop signal (ISTP) is turned on. When the interlock signal (ITL) is turned off, operation is resumed. 
The interlock signal (ITL) for normally-open contact or normally-closed contact can be selected using control 
option 3 (parameter No.0202). (The explanation in this section is for a normally-open contact.) 
When using interlock to stop the servo, deceleration uses the rapid stop time constant. 
Speed limit value
Interlock (ITL)
Interlock stop 
(ISTP)
ON
OFF
ON
OFF
Command speed
Rapid stop time 
constant
Acceleration time
constant
 
If the interlock signal is cancelled during deceleration, operation is re-started after the command speed 
decreases to 0. For this case, the interlock stop signal (ISTP) does not turn on. 
Command speed
Interlock (ITL)
Interlock stop 
(ISTP)
ON
OFF
ON
OFF
Command speed decreases to 0
and then acceleration is restarted.